HVAC REBATES - 2010

Energy Efficiency > Business > Rapid > HVAC

For information on equipment purchased in 2010, click the links below:

   > Packaged Terminal A/C and Heat Pumps

   > Unitary and Split System A/C

   > Air Source Heat Pumps

   > Ground Water-Source Heat Pumps (Open Loop)

   > Ground-Coupled Heat Pumps (Closed Loop)

   > Air Cooled Chillers

   > Water Cooled Chillers

   > Heat Pump Water Heaters

   > Thermal Storage

   > Other

   > HVAC 2010 Printer Friendly Version (PDF)

* Rebates apply only to new equipment being used to replace existing equipment or as part of a retrofit project.

Packaged Terminal Air Conditioning and Heat Pumps
  • Must have an EER rating of greater than: 12.8 - (.213 x (BTUH / 1000))
Measure Rebate
Any Size $50.00


Unitary and Split System Air Conditioning
Measure Rebate Min. Efficiency
< 65,000 BTUH $400.00/unit 14.0 SEER
65,000 — 135,000 BTUH $40.00/ton 11.0 EER
136,000 — 240,000 BTUH $40.00/ton 10.8 EER
241,000 — 760,000 BTUH $40.00/ton 10.0 EER
> 760,000 BTUH $40.00/ton 9.7 EER


Air Source Heat Pumps
Measure Rebate Min. Efficiency
< 65,000 BTUH (split) $400.00/unit 14.0 SEER
< 65,000 BTUH (single pkg) $400.00/unit 14.0 SEER
65,000 — 135,000 BTUH $40.00/ton 11.0 EER
136,000 — 240,000 BTUH $40.00/ton 10.8 EER
> 240 ,000 BTUH $40.00/ton 10.0 EER


Ground Water-Source Heat Pumps (Open Loop)
Measure Rebate Min. Efficiency
< 135,000 BTUH @ 59°F Entering Water $80.00/ton 16.2 EER


Ground-Coupled Heat Pumps (Closed Loop)
Measure Rebate Min. Efficiency
< 135,000 BTUH @ 77°F Entering Water $60.00/ton 14.1 EER


Air Cooled Chillers
Measure Rebate Min. Efficiency
Any Size $40.00/ton

9.56 EER full load

10.41 EER IPLV

The chiller efficiency rating must be based on ASHRAE 90.1-2007 chiller efficiency standards.
A manufacturer’s specification sheet with the rated EER must accompany the application.


Water Cooled Chillers
Measure Rebate Min. Efficiency
< 150 ton $40.00/ton .79 KW/ton full load
.68 KW/ton part load
150 — 300 ton $40.00/ton .72 KW/ton full load
.63 KW/ton part load
> 300 ton $40.00/ton .64 KW/ton full load
.57 KW/ton part load
The chiller efficiency rating must be based on ASHRAE 90.1-2007 chiller efficiency standards.
A manufacturer’s specification sheet with the rated KW/ton full load and IPLV must accompany the application.


Heat Pump Water Heaters
Measure Rebate Min. Efficiency
< 80 gallon tank $1,000.00 3.0 COP
80 — 150 gallon tank $2,000.00 3.0 COP
> 150 gallon tank $2,500.00 3.0 COP


Thermal Storage
Measure Rebate  
Thermal Storage Unit $100.00/KW shifted  


Other
  • VFDs are for use with supply fans, return fans, exhaust fans, water pumps and cooling tower pumps only
  • Air economizers must be installed on CEE Tier 1 or higher efficiency units
Measure Rebate Min. Efficiency
Variable frequency drives up to 50 HP $40.00/hp
60 — 100 HP $30.00/hp
Outside air economizer using two enthalpy sensors $250.00
Energy recovery ventilation (ERV) with a minimum of 450 CFM and as part of an electric-powered system $1.00/CFM ARI 1060 rating > 65% winter effectiveness
Programmable setback thermostat $20.00
HVAC occupancy sensor $30.00